TB182 Rev2 Delta Inverter Non ATC Settings VFD B
Overview
This Technical Bulletin describes how to set the parameters for Delta VFD B series inverter
To program the Delta Inverter programming parameters
Each Delta inverter parameter has 2 set of numbers Example 01 02 We will call 01 "Group Parameter" and 02 "Parameter Number "
1 Press "PROG"
2 Press the up or down arrow key to select the group parameter
3 Press "PROG"
4 Press the up or down arrow key to select the parameter number
5 Press "PROG" At this time parameter value should be blinking Use arrow key to change the value
6 Press "PROG" again to save parameter values or "Mode" to discard
7 Continue until all the parameters have been set
Delta Inverter Parameter Settings
Model VFD B
Parameter Function Setting
00 09 Control Method 0
01 00 Maximum Output Frequency F
max xxx
01 02 Maximum Output Voltage xxx
01 09 Acceleration Time 1 2 ~ 5
01 10 Deceleration Time 1 2 ~ 5
01 15 Auto Acceleration / Deceleration 1
02 00 Source of First Frequency Command 01
02 01 Source of First Operation Command 01
03 01 Multi Function Output Terminal MO1 3
03 02 Multi Function Output Terminal MO2 24
* Parameter 01 00 depends on the maximum spindle speed desired
* Parameter 01 02 depends on the motor specification Usually this information is listed on the tag of motor
* Parameter 03 01 and 03 02 is used for Zero Speed
* To reset this inverter set parameter 00 02 to 10
Â
VFD V inverter connections
R S T 3 phase power in
U V W Motor power out
FWD Spin forwards
REV Spin reverse
MI5 Reset
DCM Input common
AVI 0 10vdc input
ACM 0 10vdc common
RA Inverter fault Normally open
RC Inverter fault common
+2/B1 B2 Braking resistor
Document History
Rev2 Created on 2009 11 12
by #240