TB163 Rev1 Single Phase Operation of Centroid Controls
A phase converter is not recommended or needed for running most controls using single phase Most
3 phase motors can be operated using an Inverter for less cost than a noisy phase converter
Main control
DC servo systems made after January 1 1995 are designed to use single phase to power the main servo
control The L1 line is not used by the control It is only used to power 3 phase motors For single phase
operation make sure that power is connected to L2 and L3
AC servo systems can also be powered from L2 and L3 Single phase operation is not recommended for
systems using servomotors over 1kW Systems with only 2 axis can use up to 2kW motors although most
systems that use larger servo motors also use larger spindle motors and the use of single phase for spindle
motors over 7 5hp is not practical
Spindle motor operation with single phase
1 Spindle motors of 7 5hp or less can be run using single phase power Spindle motors higher than 7 5hp
require too much current Over 100amps to be practically run with single phase
2 An inverter is recommended for spindle operation Replacing reversing contactors with an inverter is less
expensive than a phase converter A 5hp inverter is around $450 Most controls can be set up for spindle
speed control but the inverter can be used to just turn the spindle on and off also
3 An inverter capable of single phase operation must be used The following inverters will work
* Mitsubishi FR A500 series for ATC units
* Hitachi SJ100 series
* Automation Direct GS1 and GS2
4 For other models consult the manufacturer to find out if they are capable of single phase operation
5 Oversize the inverter accordingly
3 phase Spindle motor size 1 5 Hp 2 Hp 3 Hp 5 Hp 7 5 Hp
Inverter size needed 2 HP 3 Hp 5 Hp 7 5 Hp 10 Hp
6 For proper connection of an inverter for single phase operation refer to the inverter manual Different
inverters use different connections for single phase operation
Â
To run a 3 phase flood pump using single phase an inexpensive inverter $100 can be used to run the flood
pump in place of a contactor The output of the inverter is set to 60Hz and the output on the PLC is used to
turn the inverter on and off Disconnect the original contactor control wires and connect the inverter control
wires as shown
NOTE A RTK2 PLC has 24vac internally provided on the flood output It would require the use of a 24vac
relay or contactor to turn the inverter on and off All other PLC types are a simple switch closure Except for
the RTK2 PLC disconnect the original contactor control wires and connect the inverter control wires as shown
To run a single phase flood pump the overload protector on the flood contactor must be removed and
replaced with the correct size fuses
To run a 3 phase ATC Carousel motor with a PLCIO2 using single phase an inexpensive inverter $100 can
be used to run the carousel motor The output of the inverter is set to 60Hz and the outputs on the PLC are
used to turn the inverter on and off Disconnect the original contactor control wires and connect the inverter
control wires as shown
To run a 3 phase ATC Carousel motor and flood pump with a RTK3 PLC using single phase an inexpensive
inverter $100 can be used to run the carousel motor and another inverter to run the flood pump motor The
output of the inverters is set to 60Hz and the outputs on the PLC are used to turn the inverters on and off
Disconnect the original power wires and connect the inverter control wires as shown
To use a single phase reversing carousel motor with a PLCIO2 PLC Connect the incoming single phase
power and motor wires as shown without changing the contactor control wires
To use a single phase reversing carousel motor and single phase flood pump motor with a RTK3 PLC
Connect the incoming single phase power and motors as shown
Â
Document History
Rev1 Created on 2004 01 21